IBT Modular Indirect Fired Bent Tube Heater Formulas

Heating Requirements
Input BTU/Hr =   Blower SCFM * Temp Rise * Density Factor

.80


Temp Rise =   Input BTU/Hr * .80

CFM * Density Factor


Density Factor =   1.08 +  (70-Blower Temp) * .024

10



Output BTU/Hr
Output BTU/Hr =   Input BTU/Hr * .80
 
 
 