Controls for Industrial Direct Fired Recirculating Heaters (80/20)
|
|
|
|
Day and Night Control Option consists of a DAY/NIGHT switch that positions
the fresh-air damper, controlled by either the photo-helic or manual-pot
control during day operation and then positions the dampers for 20% fresh
air and 80% return-air bypass during the night.
|
|
|
Manual Positioning Control Option consists of a room-mounted potentiometer
that adjusts manually from 20% to 100% fresh air to satisfy changing building
make-up requirements. When the system selector is in the off position, the return-air
bypass damper closes by the spring-return damper motor.
Humidity Control Option: a modulating-humidistat position damper motor uses
fresh air to lower space humidity.
|
|
|
Static-Pressure Control Option
consists of a room-mounted static controller with an outdoor sensor. The
controller can be set to the building's minimum and maximum
static-pressure requirements. The damper proportions the fresh-air and
return-air dampers to maintain static pressure between the minimum and
maximum settings.
A visual indicator of the building static pressure is incorporated in
the controller. When the System Selector Switch is in the OFF position, a switch
circuit powers the return-air bypass to the closed position.
|
|